Transformer Oil Filtration Plants
Feature:
- Break Down Voltage from 20 KV to more then 50 kV
- Filtration level upto < 1 micron.
- Moisture contents - from 50 -100 PPM to < 5 PPM.
- Gas contents - upto < 0.05% by volume.
- Neutralization value- < 0.1 mg of KOH / gm.
- Plants with minimum and easy maintenance.
- Low Operating cost due to high vacuum filtration with rotary oil sealed pumps.
- Available in Portable & Mobile versions.
Application:
- Oil transfer & circulation system:
The plants will have two pumps for oil transfer and circulation. Both
pumps will be positive displacement gear type, directly coupled with
electric motor. The plants will have necessary valves and piping to
ensure easy operation and maintenance.
- Heating System:
The plants will have an insulated heater chamber with indirect type
bobbin heater for heating of oil up to 80° C. However the working
temperature for filtration will be 55° C. Heater pipes will be finned
to have more efficient heat transfer. Temperature will be controlled
with thermostat or Digital Temperature indicator cum controller.
- Filtration System: The filtration system is suitable for removing suspended particles such as colloidal carbon, oxidation sludge, dirt, rust.
- Degassing chamber and vacuum system:
The oil dispersed while passing through fine filter will be sprayed on
reaching ring tray to have an exposure of oil film to vacuum, because
of which moisture removal rate will be increased. Degassing chamber
will be evacuated with rotary oil sealed vacuum pump moisture trap,
valves, etc.
- This plants are suitable for Hydraulic Oil, Thermic Fluid, etc.
Technical Specification:
| Flow Rate -
LPH |
600 |
1200 |
2400 |
4500 |
6000 |
| Heater
Capacity- K.W. |
6 |
18 |
45 |
63 |
81 |
| Single stage
Rotary Oil sealed vacuum Pump. |
100
LPM |
300
LPM |
500
LPM |
1000
LPM |
2000
LPM |
| Total Power
Required |
7.5
K.W. |
20
KW. |
50
kW |
70
kW |
96
kW |
| Fine
Filter Elements Moulded Cellulose |
|
| Filter Fineness |
3 / 0.5
µ |
|
Dimensions
In Mtrs. |
| Stationery
Unit, W / L / H |
0.6/0.9/1.4 |
0.8/1.2/1.5 |
1.0/1.8/1.6 |
1.2/2.0/1.7 |
1.2/2.4/1.8 |
| Unit on
Castors, W / H / L |
0.6/0.9/1..6 |
0.8/1.2/1.7 |
1.0/1.8/1.9 |
1.2/2.0/2.0 |
1.2/2.4/2.1 |
| Unit of
Trailers, W / H / L |
1.2/1.4/2.1 |
1.4/1.7/2.2 |
1.6/2.2/2.4 |
1.8/2.4/2.6 |
1.8/2.8/2.6 |
| Max Oil
Content in Transformer - Ltrs |
1000 |
2500 |
7500 |
20000 |
35000 |
|